β¨ Energy Delivery Efficiency Statistics
8 FEBRUARY NEW ZEALAND GAZETTE
Disclosure of energy delivery efficiency performance measures and statistics pursuant to Regulation 15 and Part II of the First Schedule of the Electricity (Information Disclosure) Regulations 1994.
| Energy Delivery Efficiency Measures | 1997/98 | 1996/97 | 1995/96 | 1994/95 |
|---|---|---|---|---|
| Load Factor | 57.7% | 58.1% | 57.5% | 56.8% |
| Loss Ratio | 5.0% | 5.0% | 5.0% | 5.5% |
| Capacity Utilisation | 40.0% | 38.27% | 39.1% | 40.7% |
| Statistics | 1997/98 | 1996/97 | 1995/96 | 1994/95 |
|------------------------------------|----------|----------|
| System Information (km) | 33kV | 33kV | 33kV | 33kV |
| System length breakdown | 22.5 | 22.5 | 22.5 | 22.5 |
| Underground circuit length | 9.9 | 9.9 | 9.9 | 9.9 |
| Overhead circuit length | 12.6 | 12.6 | 12.6 | 12.6 |
| System Information (km) | 11kV | 11kV | 11kV | 11kV |
| System length breakdown | 79.3 | 79.1 | 79.0 | 78.5 |
| Underground circuit length | 68.2 | 67.9 | 67.8 | 67.3 |
| Overhead circuit length | 11.1 | 11.2 | 11.2 | 11.2 |
| System Information (km) | 400V | 400V | 400V | 400V |
| System length breakdown | 115.8 | 115.2 | 114.3 | 112.0 |
| Underground circuit length | 89.1 | 88.0 | 86.9 | 84.6 |
| Overhead circuit length | 26.7 | 27.2 | 27.4 | 27.4 |
| System Information (km) | Total| Total| Total| Total|
| System length breakdown | 217.6 | 216.8 | 215.8 | 213.0 |
| Underground circuit length | 167.2 | 165.8 | 164.6 | 161.8 |
| Overhead circuit length | 50.4 | 51.0 | 51.2 | 51.2 |
| Transformer capacity (kVA) | 70,470 | 72,520 | 71,820 | 66,815 |
| Maximum demand (kilowatts) | 28,185 | 28,095 | 28,100 | 27,200 |
| Total electricity supplied (kWh) | 142,458,214 | 143,529,169 | 141,566,178 | 135,441,303 |
| Total conveyed-non-associated parties | 0 | 0 | 0 | 0 |
| Total customers | 8,341 | 8,359 | 8,322 | 8,242 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1999, No 17
NZLII —
NZ Gazette 1999, No 17
β¨ LLM interpretation of page content
π
Energy Delivery Efficiency Performance Measures and Statistics
(continued from previous page)
π Trade, Customs & IndustryEnergy Delivery, Efficiency Measures, Statistics, Load Factor, Loss Ratio, Capacity Utilisation, System Information, Transformer Capacity, Maximum Demand, Electricity Supply