✨ Electricity Reliability Performance Measures




31 AUGUST NEW ZEALAND GAZETTE 2511

Years ended 31 March
1999 1998 1997 1996

(9) SAIDI targets for the following financial year
(a) Planned Interruption by the line owner Class B 60
(b) Unplanned Interruption originating from the works of the line owner Class C 100

(10) Average SAIDI Interruption targets for the following financial year and subsequent 4 financial years
(a) Planned Interruption by the line owner Class B 58
(b) Unplanned Interruption originating from the works of the line owner Class C 96

(11) The SAIDI for total of interruptions within each interruption class
Class A 0 0 0 0
Class B 57.15 55 77.9 109
Class C 144.7 84.2 95.5 117
Class D 0 0 3.6 2
Class E 0 0 0 0
Class F 0 0 0 0
Class G 0 0 0 0

(12) The SAIFI for total of interruptions
3.47 2.6 3.5 5.4

(13) SAIFI targets for the following financial year
(a) Planned Interruption by the line owner Class B 0.39
(b) Unplanned Interruption originating from the works of the line owner Class C 2.70

(14) Average SAIFI targets for the following financial year and subsequent 4 financial years
(a) Planned Interruption by the line owner Class B 0.38
(b) Unplanned Interruption originating from the works of the line owner Class C 2.69

(15) The SAIFI for total of interruptions within each interruption class -
Class A 0 0 0 0
Class B 0.38 0.4 0.5 1
Class C 3.09 2.2 2.7 4.4
Class D 0 0 0.3 0
Class E 0 0 0 0
Class F 0 0 0 0
Class G 0 0 0 0

(16) The CAIDI for total interruptions
198.04 53.5 52.1 49



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1999, No 105


NZLII PDF NZ Gazette 1999, No 105





✨ LLM interpretation of page content

🏭 Regulation 22: Reliability Performance Measures (continued from previous page)

🏭 Trade, Customs & Industry
Reliability, Performance Measures, Electricity, Regulations, SAIDI, SAIFI, CAIDI