β¨ Financial and Performance Indicators
31 AUGUST NEW ZEALAND GAZETTE
SCANPOWER LIMITED
PERFORMANCE INDICATORS
FOR THE YEAR ENDED 31 MARCH 1998
1. FINANCIAL PERFORMANCE MEASURES
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| Accounting Return on Total Assets | 0.45% | 0.12% | 1.44% | 1.67% |
| Accounting Return on Equity | -0.66% | -0.71% | -1.55% | -1.95% |
| Accounting Rate of Profit | -0.61% | -0.70% | -1.54% | -1.83% |
2. EFFICIENCY PERFORMANCE INDICATORS
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| Direct Line Costs per Kilometre | $959 | $899 | $866 | $693 |
| Indirect Line Costs per Customer | $63 | $68 | $57 | $61 |
3. ENERGY DELIVERY EFFICIENCY PERFORMANCE MEASURES
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| Load Factor | 62.00% | 66.50% | 66.55% | 64.11% |
| Loss Ratio | 7.28% | 7.34% | 7.95% | 7.79% |
| Capacity Utilisation | 27.55% | 26.32% | 26.04% | 26.06% |
3A. OPTIMISED DEPRIVAL VALUATION
The Optimised Deprival Valuation of the Lines Business Assets as at 31 March 1998 was $19,109,668.
4. STATISTICS
Circuit Length of Overhead System
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 11 KV | 766 | 765 | 765 | 789 |
| 400 V | 196 | 197 | 197 | 189 |
| Total | 962 | 962 | 962 | 978 |
Circuit Length of Underground System
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 400 V | 35 | 33 | 32 | 31 |
| Total | 35 | 33 | 32 | 31 |
System Length
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 11 KV | 766 | 765 | 765 | 789 |
| 400 V | 231 | 230 | 229 | 220 |
| Total | 997 | 995 | 994 | 1,009 |
Transformer Capacity
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 54,317 | 53,157 | 54,425 | 54,055 |
Maximum Demand KW
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 14,967 | 13,971 | 14,176 | 14,089 |
Total Electricity Supplied from Systems (Sales) Kwh
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 75,285,058 | 75,584,065 | 76,281,299 | 72,965,022 |
Electricity on behalf of other entities
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| - | - | - | - |
Total Customers
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 6,700 | 6,700 | 6,700 | 6,713 |
Number of Faults per 100 circuit kilometre overhead
| 1998 | 1997 | 1996 | 1995 | |
|---|---|---|---|---|
| 11 KV | 10 | 15 | 9 | 11 |
| Total | 10 | 15 | 9 | 11 |
Total Interruptions 1998
| CLASS | A | B | C | D | E | F | G | TOTAL |
|---|---|---|---|---|---|---|---|---|
| SAIDI | 49 | 44.37 | 64.8 | 78 | 0 | 0 | 0 | 236.17 |
| SAIFI | 0.234 | 0.275 | 0.63 | 0.8 | 0 | 0 | 1.9415 | |
| CAIDI | 209 | 160 | 103 | 98 | 0 | 0 | 0 | 121.6 |
| INTERRUPTIONS | 1 | 106 | 74 | 2 | 0 | 0 | 0 | 183 |
Total Interruptions 1997
| CLASS | A | B | C | D | E | F | G | TOTAL |
|---|---|---|---|---|---|---|---|---|
| SAIDI | 28 | 74.68 | 50.58 | 18.55 | 0 | 0 | 0 | 171.81 |
| SAIFI | 0.23 | 0.5975 | 0.5517 | 0.324 | 0 | 0 | 1.7032 | |
| CAIDI | 122 | 125 | 57 | 57 | 0 | 0 | 0 | 101 |
| INTERRUPTIONS | 1 | 99 | 113 | 2 | 0 | 0 | 0 | 215 |
Total Interruptions 1996
| CLASS | A | B | C | D | E | F | G | TOTAL |
|---|---|---|---|---|---|---|---|---|
| SAIDI | 49.15 | 41.66 | 32.63 | 0 | 0 | 0 | 0 | 123.44 |
| SAIFI | 0.2324 | 0.579 | 0 | 0 | 0 | 0 | 1.314 | |
| CAIDI | 214 | 129 | 56 | 0 | 0 | 0 | 0 | 109 |
| INTERRUPTIONS | 1 | 127 | 68 | 0 | 0 | 0 | 0 | 196 |
Total Interruptions 1995
| CLASS | A | B | C | D | E | F | G | TOTAL |
|---|---|---|---|---|---|---|---|---|
| SAIDI | 58 | 32 | 41.4 | 31 | 0 | 0 | 0 | 160.4 |
| SAIFI | 0.234 | 0.476 | 0.708 | 1.91 | 0 | 0 | 3.328 | |
| CAIDI | 240 | 67 | 58 | 16 | 0 | 0 | 0 | 48 |
| INTERRUPTIONS | 1 | 88 | 84 | 5 | 0 | 0 | 0 | 178 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1998, No 127
NZLII —
NZ Gazette 1998, No 127
β¨ LLM interpretation of page content
π
Certificate of Financial Statements for Scanpower Limited
(continued from previous page)
π Trade, Customs & Industry14 August 1998
Financial Statements, Audit, Electricity Information Disclosure, Scanpower Limited, Regulations