✨ Electricity Reliability Statistics
NEW ZEALAND GAZETTE
No. 123
PERFORMANCE MEASURES AND OTHER INFORMATION - PART IV
Regulation 16
Reliability Performance Measures to be Disclosed by Line
| 1995 | 1996 | 1997 | 1998 | |
|---|---|---|---|---|
| 1 TOTAL NUMBER OF INTERRUPTIONS: | ||||
| Class A | 1 | 0 | 2 | 1 |
| Class B | 78 | 37 | 40 | 53 |
| Class C | 350 | 511 | 450 | 164 |
| Class D | 10 | 7 | 2 | 4 |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 0 | 0 | 0 |
| Total | 439 | 555 | 494 | 222 |
| 1995 | 1996 | 1997 | 1998 | |
|---|---|---|---|---|
| 2 TOTAL NUMBER OF FAULTS PER 100 CIRCUIT KM | ||||
| Total | 19 | 15 | 12 | 11 |
| 33kV | 6 | 1 | 14 | 12 |
| 11kV | 13 | 14 | 9 | 12 |
| This breakdown is an estimate |
| 1995 | 1996 | 1997 | 1998 | |
|---|---|---|---|---|
| 3 TOTAL NUMBER OF FAULTS PER 100 CIRCUIT KM OF UNDERGROUND | ||||
| Total | 4 | 20 | 22 | 3 |
| 33kV | 0 | 0 | 0 | 0 |
| 11kV | 4 | 20 | 9 | 3 |
| This breakdown is an estimate |
| 1995 | 1996 | 1997 | 1998 | |
|---|---|---|---|---|
| 4 TOTAL NUMBER OF FAULTS PER 100 CIRCUIT KM OF OVERHEAD | ||||
| Total | 16 | 19 | 14 | 12 |
| 33kV | 3 | 2 | 14 | 12 |
| 11kV | 13 | 17 | 9 | 12 |
| This breakdown is an estimate |
| 5 THE SAIDI FOR THE TOTAL NUMBER OF INTERRUPTIONS | 336 | 313 | 367 | 271 |
| 6 THE SAIDI FOR THE TOTAL NUMBER OF INTERRUPTIONS WITHIN EACH CLASS | | | | |
| Class A | 37 | 0 | 14 | 51 |
| Class B | 82 | 79 | 91 | 64 |
| Class C | 203 | 223 | 215 | 164 |
| Class D | 11 | 11 | 47 | 21 |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 0 | 0 | 0 |
| 7 THE SAIFI FOR THE TOTAL NUMBER OF INTERRUPTIONS | 5.6 | 3.7 | 3.8 | 4.0 |
| 8 THE SAIFI FOR THE TOTAL NUMBER OF INTERRUPTIONS WITHIN EACH CLASS | | | | |
| Class A | 0.1 | 0.0 | 0.1 | 0.2 |
| Class B | 0.5 | 0.4 | 0.4 | 0.5 |
| Class C | 3.9 | 2.5 | 3.1 | 3.1 |
| Class D | 1.0 | 0.8 | 0.2 | 0.2 |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 0 | 0 | 0 |
| 9 THE CAIDI FOR THE TOTAL OF ALL INTERRUPTIONS | 59 | 85 | 98 | 410 |
| 10 THE CAIDI FOR THE TOTAL OF ALL INTERRUPTIONS WITHIN EACH CLASS | | | | |
| Class A | 240 | 0 | 186 | 230 |
| Class B | 157 | 203 | 227 | 118 |
| Class C | 52 | 89 | 71 | 53 |
| Class D | 11 | 14 | 196 | 110 |
| Class E | 0 | 0 | 0 | 0 |
| Class F | 0 | 0 | 0 | 0 |
| Class G | 0 | 0 | 0 | 0 |
Note: As per Regulation 16(2)(b) Reliability Performance Measures for 1998 have been calculated excluding low voltage circuits and 11kV fuses supplying less than three customers.
PUBLISHED BY AUTHORITY OF DEPARTMENT OF INTERNAL AFFAIRS:
GP LEGISLATION SERVICES. WELLINGTON, NEW ZEALAND—1998
DEPARTMENT OF INTERNAL AFFAIRS
TE TARI TAIWHENUA
ISSN 0111-5650
Price $3.95 (inc. G.S.T.)
31507—98A
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1998, No 123
NZLII —
NZ Gazette 1998, No 123
✨ LLM interpretation of page content
🏭
Energy Delivery Efficiency Performance Measures and Statistics
(continued from previous page)
🏭 Trade, Customs & IndustryEnergy Efficiency, Electricity Statistics, Load Factor, Loss Ratio, Circuit Length, Transformer Capacity, Maximum Demand, Electricity Supply, Reliability, Interruptions, Faults, SAIDI, SAIFI, CAIDI