✨ Electricity Reliability Performance Measures




NEW ZEALAND GAZETTE

No. 116

Year ended 31 March

1998 1997 1996 1995

Regulation 16:

(1) Reliability performance measures

Class A | 0 | 0 | 0 | 0
Class B | 343 | 511 | 350 | 290
Class C | 257 | 385 | 369 | 300
Class D | 4 | 10 | 12 | 4
Class E | 0 | 0 | 0 | 0
Class F | 0 | 0 | 0 | 0
Class G | 0 | 0 | 0 | 0
Total | 604 | 906 | 731 | 594

(2) Total number of faults per 100 circuit kilometres prescribed voltage electric lines.

                  | 10.0 | 14.7 | 14.4 | 12.1

(3) Total number of faults per 100 circuit kilometres of underground prescribed voltage electric lines.

  • 33kV | 0 | 0 | 0 | 0
  • 11kV | 0 | 16.7 | 4.8 | 33.3
  • Total | 0 | 16.7 | 4.8 | 33.3

(4) Total number of faults per 100 circuit kilometres of overhead prescribed voltage electric lines.

  • 33kV | 15.7 | 13.2 | 16.7 | 9.8
  • 11kV | 9.5 | 14.7 | 15.0 | 12.3
  • Total | 10.0 | 14.7 | 14.5 | 12.1

(5) The SAIDI for total of interruptions

                  | 662.2| 866.3| 714.92| 886.4

(6) The SAIDI for total of interruptions within each interruptions class -

Class A | 0 | 0 | 0 | 0
Class B | 334.5| 368.7| 331.05| 398.7
Class C | 303.8| 460.5| 370.15| 468.8
Class D | 23.9 | 37.09| 13.71 | 18.8
Class E | 0 | 0 | 0 | 0
Class F | 0 | 0 | 0 | 0
Class G | 0 | 0 | 0 | 0

(7) The SAIFI for total of interruptions

                  | 9.3  | 11.00| 11.03| 9.59

(8) The SAIFI for total of interruptions within each interruption class -

Class A | 0 | 0 | 0 | 0
Class B | 1.79 | 1.90 | 1.68 | 1.52
Class C | 6.98 | 7.76 | 9.08 | 7.59
Class D | 0.54 | 1.34 | 0.27 | 0.47
Class E | 0 | 0 | 0 | 0
Class F | 0 | 0 | 0 | 0
Class G | 0 | 0 | 0 | 0

(9) The CAIDI for total of interruptions

                  | 71.18| 78.78| 64.81| 92.43

(10) The CAIDI for total interruptions within each interruption class -

Class A | - | - | - | -
Class B | 186.73| 194.30| 196.73| 262.33
Class C | 43.55| 59.35| 40.76| 61.77
Class D | 44.54| 27.68| 51.37| 40.04
Class E | - | - | - | -
Class F | - | - | - | -
Class G | - | - | - | -



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1998, No 116


NZLII PDF NZ Gazette 1998, No 116





✨ LLM interpretation of page content

🏭 Waitomo Energy Services Limited Financial Performance Statement (continued from previous page)

🏭 Trade, Customs & Industry
Electricity, Reliability Performance, Faults, Interruptions, SAIDI, SAIFI, CAIDI, Circuit Kilometres