β¨ Electricity Network Reliability Statistics
4 AUGUST
NEW ZEALAND GAZETTE
6 Reliability Performance Measures
| Number of Interruptions | 1998 | 1997 | 1996 | 1995 |
|---|---|---|---|---|
| A Planned Transpower | 0 | 0 | 0 | 0 |
| B Planned Distributor | 27 | 56 | 21 | 57 |
| C Unplanned Distributor | 139 | 88 | 68 | 117 |
| D Unplanned Transpower | 0 | 0 | 1 | 0 |
| E Unplanned ECNZ | 0 | 0 | 0 | 0 |
| F Unplanned Generator | 0 | 0 | 0 | 0 |
| G Unplanned Other | 0 | 0 | 0 | 0 |
| Total | 166 | 144 | 90 | 174 |
Total Number of Faults per 100km of HV System | 8.33 | 8.69 | 5.46 | 10.58 |
| Total Number of Faults per 100km of Underground HV Circuit | | | | |
|----------------------------------------------------------------|------|
| 33kV | 0.00 | 0.00 | 0.00 | 0.14 |
| 11kV | 10.31| 10.25| 11.50| 35.63|
| Total | 10.15| 10.10| 11.32| 35.32|
| Total Number of Faults per 100km of Overhead HV Circuit | | | | |
|-----------------------------------------------------------|------|
| 33kV | 4.35 | 0.00 | 1.45 | 0.72 |
| 11kV | 8.68 | 5.74 | 5.76 | 11.22|
| Total | 8.31 | 5.25 | 5.40 | 10.33|
SAIDI
| Total Interruptions | 1998 | 1997 | 1996 | 1995 |
|---|---|---|---|---|
| Total Interruptions | 87.41 | 103.58 | 90.74 | 127.50 |
| A Planned Transpower | 0.00 | 0.00 | 0.00 | 0.00 |
| B Planned Distributor | 14.84 | 49.94 | 27.93 | 73.56 |
| C Unplanned Distributor | 72.57 | 53.64 | 61.11 | 53.94 |
| D Unplanned Transpower | 0.00 | 0.00 | 1.69 | 0.00 |
| E Unplanned ECNZ | 0.00 | 0.00 | 0.00 | 0.00 |
| F Unplanned Generator | 0.00 | 0.00 | 0.00 | 0.00 |
| G Unplanned Other | 0.00 | 0.00 | 0.00 | 0.00 |
SAIFI
| Total Interruptions | 1998 | 1997 | 1996 | 1995 |
|---|---|---|---|---|
| Total Interruptions | 1.45 | 0.93 | 1.19 | 0.92 |
| A Planned Transpower | 0.00 | 0.00 | 0.00 | 0.00 |
| B Planned Distributor | 0.13 | 0.31 | 0.20 | 0.52 |
| C Unplanned Distributor | 1.32 | 0.62 | 0.85 | 0.40 |
| D Unplanned Transpower | 0.00 | 0.00 | 0.14 | 0.00 |
| E Unplanned ECNZ | 0.00 | 0.00 | 0.00 | 0.00 |
| F Unplanned Generator | 0.00 | 0.00 | 0.00 | 0.00 |
| G Unplanned Other | 0.00 | 0.00 | 0.00 | 0.00 |
CAIDI
| Total Interruptions | 1998 | 1997 | 1996 | 1995 |
|---|---|---|---|---|
| Total Interruptions | 60.32 | 110.90 | 76.05 | 138.05 |
| A Planned Transpower | 0.00 | 0.00 | 0.00 | 0.00 |
| B Planned Distributor | 115.46 | 160.16 | 138.10 | 141.11 |
| C Unplanned Distributor | 54.96 | 86.22 | 71.90 | 134.10 |
| D Unplanned Transpower | 0.00 | 0.00 | 12.00 | 0.00 |
| E Unplanned ECNZ | 0.00 | 0.00 | 0.00 | 0.00 |
| F Unplanned Generator | 0.00 | 0.00 | 0.00 | 0.00 |
| G Unplanned Other | 0.00 | 0.00 | 0.00 | 0.00 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1998, No 105
NZLII —
NZ Gazette 1998, No 105