✨ Electricity Reliability Statistics




18 AUGUST

NEW ZEALAND GAZETTE

2157

  1. The SAIDI for total of interruptions
1997 1996 1995
86 182 140
  1. The SAIDI for total of interruptions within each interruption class -
Class 1997 1996 1995
A 28 37 54
B 24 14 19
C 23 58 66
D 11 73 1
E 0 0 0
F 0 0 0
G 0 0 0
  1. The SAIFI for total of interruptions
1997 1996 1995
2.62 2.66 1.43
  1. The SAIFI for total of interruptions within each interruption class -
Class 1997 1996 1995
A 0.11 0.11 0.19
B 0.04 0.04 0.14
C 0.71 0.72 1.1
D 1.77 1.79 0.03
E 0 0 0
F 0 0 0
G 0 0 0
  1. The CAIDI for total of interruptions
1997 1996 1995
33 69 98
  1. The CAIDI for total of interruptions within each interruption class -
Class 1997 1996 1995
A 258 334 280
B 650 383 129
C 32 81 60
D 6 41 40
E 0 0 0
F 0 0 0
G 0 0 0