Electricity Reliability Statistics




11 JULY

NEW ZEALAND GAZETTE

1735

PERFORMANCE MEASURES AND OTHER INFORMATION

FOR YEAR ENDED 31 MARCH 1997

5. Reliability Performance Measures

➊ Total number of Interruptions:

1997 1996 1995
Class B 17 12 13
Class C 25 28 24
Total Other - - -
Total 42 40 37

➋ Faults per 100 circuit Km:

1997 1996 1995
33kV 11kV Total 33kV 11kV Total
Total number - - 3.6 - - 4.1
Underground 17.6 6.9 8.2 6.3 4.3 4.6
Overhead 370.4 26.3 27.3 - 50.4 50.2

➌ SAIDI number of Interruptions by class:

1997 1996 1995
Class B 10.15 4.4 12.9
Class C 67.89 52.6 58.4
Total Other - - -
Total 78.04 57.0 71.3

➍ SAIFI number of Interruptions by class:

1997 1996 1995
Class B .071 .042 .083
Class C 2.147 .935 1.050
Total Other - - -
Total 2.218 .978 1.133

➎ CAIDI number of Interruptions by class:

1997 1996 1995
Class B 143 105 155
Class C 32 56 56
Total Other - - -
Total 35 58 63