✨ Electricity Reliability Performance Measures




3058 NEW ZEALAND GAZETTE No. 131

Disclosure of reliability performance measures pursuant to regulation 16 of the Electricity (Information Disclosure) Regulations 1994

  1. Total number of interruptions, together with a breakdown of that total according to interruption class
1997 1996 1995
Classes A, E-G 0 0 0
Class B 181 227 260
Class C 393 325 459
Class D 0 3 0
TOTAL 574 555 719
  1. Total number of faults per 100 circuit kilometres of prescribed voltage electric line

33.70 (1996 - 32.77) (1995 - 50.64)

  1. The total number of faults per 100 circuit kilometres of underground prescribed voltage electric line, together with a breakdown of that total according to different line voltages
1997 1996 1995
33kV 0 0 0
11kV 0 12.5 6.93
Overall 0 10.0 4.69
  1. The total number of faults per 100 circuit kilometres of overhead prescribed voltage electric line, together with a breakdown of that total according to different line voltages
1997 1996 1995
33kV 5.56 7.64 3.36
11kV 38.41 37.52 59.40
Overall 34.28 33.10 51.44
  1. The SAIDI for the total of interruptions is calculated in accordance with the following formula:

$$
\frac{a}{b}
$$

Where:

a is the sum obtained by adding together the interruption duration factors for all interruptions

b is the total customers

213.18 (1996 - 333.66) (1995 - 250.91)

  1. The SAIDI for the total of interruptions within each interruption class is calculated in accordance with the following formula:

$$
\frac{a}{b}
$$

Where:

a is the sum obtained by adding together the interruption duration factors for all interruptions within the particular



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1997, No 131


NZLII PDF NZ Gazette 1997, No 131





✨ LLM interpretation of page content

🏭 Disclosure of reliability performance measures pursuant to regulation 16 of the Electricity (Information Disclosure) Regulations 1994 (continued from previous page)

🏭 Trade, Customs & Industry
Electricity, Reliability Performance, Interruptions, Faults, SAIDI, Regulations