SYSTEM RELIABILITY FOR 1994.95
Disclosure by line owners of reliability performance measures as required by Regulation 16 of the Electricity (Information Disclosure) Regulations 1994
Information applies from 1-Apr-94 to 31-Mar-95
Part IV 1. of the first schedule
| Interruption class | Number |
|---|---|
| A. Planned Trans Power | 0 |
| B. Planned Westpower | 98 |
| C. Unplanned Westpower | 220 |
| D. Unplanned Trans Power | 10 |
| E. Unplanned ECNZ generation | 0 |
| F. Unplanned Westpower generation | 8 |
| G. Other interruptions | 0 |
| Total interruptions | 336 |
Part IV 2. 3. and 4. of the first schedule
Calculation of Frequencies of Line and Cable Faults
| Nominal Voltage | OVERHEAD LINES | UNDERGROUND CABLES | TOTAL |
|---|---|---|---|
| No of Faults | Length (km) | Faults per 100 km | |
| 110 kV | 0 | 0.0 | 0.00 |
| 66kV / 50kV | 4 | 23.8 | 16.83 |
| 33kV | 9 | 107.5 | 8.37 |
| 22kV | 0 | 0.0 | 0.00 |
| 11kV | 186 | 1470.9 | 12.65 |
| 6.6kV | 0 | 0.0 | 0.00 |
| 3.3kV | 0 | 0.0 | 0.00 |
| Sub Totals | 199 | 1602.2 | 12.42 |
| 400 Volt | 250.0 | ||
| Totals | 1852.2 |
The number of interruptions includes an estimation of 26 from DDO fuses replaced after lightning storms
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1995, No 95
NZLII —
NZ Gazette 1995, No 95
β¨ LLM interpretation of page content
π°
Certification of Westpower Limited's Performance Measures
(continued from previous page)
π° Finance & Revenue18 August 1995
Audit, Certification, Performance Measures, Financial, Westpower Limited
π° Westpower Limited System Reliability for 1994-95
π° Finance & RevenueReliability, Performance Measures, Electricity, Westpower Limited