NEW ZEALAND GAZETTE
No. 93
Disclosure of reliability performance measures under regulation 16 of the Electricity (Information Disclosure) Regulations 1994
1 Total number of interruptions
Class A - Planned interruptions caused by Transpower 0
Class B - Planned interruptions by Line Owners 309
Class C - Unplanned interruptions by Line Owners 119
Class D - Unplanned interruptions caused by Transpower 2
Class E - Unplanned interruptions caused by generation by ECNZ 0
Class F - Unplanned interruptions caused by other generation 0
Class G - Any loss of supply not covered by classes A to F 0
Total 430
2 The total number of faults per 100 circuit kilometers of prescribed voltage electric line
11kV 8.95
3 The total number of faults per 100 circuit kilometers of underground prescribed voltage electric line
11kV 0.00
4 The total number of faults per 100 circuit kilometers of overhead prescribed voltage electric line
11kV 9.22
5 The SAIDI for the total number of interruptions 411.53
6 The SAIDI for the total number of interruptions within each interruption class
Class A - Planned interruptions caused by Transpower 0.00
Class B - Planned interruptions by Line Owners 104.97
Class C - Unplanned interruptions by Line Owners 257.10
Class D - Unplanned interruptions caused by Transpower 49.46
Class E - Unplanned interruptions caused by generation by ECNZ 0.00
Class F - Unplanned interruptions caused by other generation 0.00
Class G - Any loss of supply not covered by classes A to F 0.00
7 The SAIFI for the total number of interruptions 5.66
8 The SAIFI for the total number of interruptions within each interruption class
Class A - Planned interruptions caused by Transpower 0.00
Class B - Planned interruptions by Line Owners 0.59
Class C - Unplanned interruptions by Line Owners 3.97
Class D - Unplanned interruptions caused by Transpower 1.10
Class E - Unplanned interruptions caused by generation by ECNZ 0.00
Class F - Unplanned interruptions caused by other generation 0.00
Class G - Any loss of supply not covered by classes A to F 0.00
9 The CAIDI for the total number of interruptions 73
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1995, No 93
NZLII —
NZ Gazette 1995, No 93
β¨ LLM interpretation of page content
π
Disclosure of reliability performance measures under regulation 16 of the Electricity (Information Disclosure) Regulations 1994
(continued from previous page)
π Trade, Customs & IndustryReliability Performance, Interruptions, Faults, SAIDI, SAIFI, CAIDI, Electricity, Transpower, Line Owners