β¨ Electricity Reliability Statistics
2838
NEW ZEALAND GAZETTE
No. 93
(3) Total number of faults per 100 km of prescribed voltage underground line
33 kV system 0
11 kV system 2.56
6.6 kV system 5.92
Total Number 2.84
(4) Total number of faults per 100 km of prescribed voltage overhead line
33 kV system 12.77
11 kV system 28.64
6.6 kV system 16.74
Total Number 22.44
| NETWORK or GENERATION OWNER | CLASSIFICATION OF INTERRUPTIONS | SAIDI | SAIFI | CAIDI |
|---|---|---|---|---|
| Electricity Distributor | Class B Planned Shutdowns | 101.17 | 0.6 | 168.88 |
| Class C Unplanned Cuts | 104.52 | 1.95 | 53.97 | |
| Subtotal | 205.69 | 2.54 | 81.12 | |
| TransPower | Class A Planned Shutdowns | 0 | 0 | 0 |
| Class D Unplanned Cuts | 5.45 | 0.29 | 19.13 | |
| Subtotal | 5.45 | 0.29 | 19.13 | |
| Generator ECNZ | Class G Planned Shutdowns | 0 | 0 | 0 |
| Class E Unplanned Cuts | 0 | 0 | 0 | |
| Subtotal | 0 | 0 | 0 | |
| Other Distributor or Generator | Class G Planned Shutdowns | 0 | 0 | 0 |
| Class F Unplanned Cuts | 0 | 0 | 0 | |
| Subtotal | 0 | 0 | 0 | |
| TOTALS | Planned Shutdowns | 101.17 | 0.60 | 168.88 |
| Unplanned Cuts | 109.97 | 2.22 | 49.50 | |
| TOTAL | 211.14 | 2.82 | 74.86 |