TRUSTPOWER LIMITED
INFORMATION DISCLOSURE LINE OWNERS
FOR THE YEAR ENDED 31 MARCH 1995
| REG # | 1st SCH | Part | IV |
|---|---|---|---|
| 16(1) |
Reliability performance measures:
-
Total Number of Interruptions
Class B ... 247
Class C ... 144
All Other Classes ... 0
Total ... 391
-
Total number of faults per 100 Km of prescribed voltage electric line ... 21.75
-
Total number of faults per 100 Km of underground prescribed voltage electric line by nominal line voltage
Total ... 3.15
33kv ... 0
11kv ... 3.16
-
Total number of faults per 100 Km of overhead prescribed voltage electric line by nominal line voltage
Total ... 25.84
33kv ... 12.68
11kv ... 8.67
-
SAIDI for total number of interruptions ... 302.71
-
SAIDI for total number of interruptions within each interruption class
Class B ... 136.87
Class C ... 165.84
-
SAIFI for total number of interruptions ... 3.34
-
SAIFI for total number of interruptions within each interruption class
Class B ... 0.76
Class C ... 2.58
-
CAIDI for total of all interruptions ... 90.67
-
CAIDI for total number of interruptions within each interruption class
Class B ... 180.61
Class C ... 64.26