β¨ Electricity Reliability Performance Measures
NEW ZEALAND GAZETTE
No. 91
Class D 17
Class E 0
Class F 0
Class G 0
- The SAIFI for the total number of interruptions, which shall be calculated in accordance with the following formula:
$$
\frac{a}{b}
$$
where -
a is the sum obtained by adding together the number of electricity customers affected by each of those interruptions; and
b is the total customers
SAIFI total interruptions = 4.9
- The SAIFI for the total number of interruptions within each interruption class, which shall be calculated in accordance with the following formula:
$$
\frac{a}{b}
$$
where -
a is the sum obtained by adding together the number of electricity customers affected by each of those interruptions within that interruption class; and
b is the total customers
| Class | |
|---|---|
| Class A | 0.1 |
| Class B | 1.1 |
| Class C | 3.3 |
| Class D | 0.4 |
| Class E | 0.0 |
| Class F | 0.0 |
| Class G | 0.0 |
- The CAIDI for the total of all interruptions, which shall be calculated in accordance with the following formula:
$$
\frac{a}{b}
$$
where -
a is the sum obtained by adding together the interruption duration factors for all interruptions; and
b is the sum obtained by adding together the number of electricity customers affected by each of those interruptions.
CAIDI total interruptions = 76
- The CAIDI for the total number of interruptions within each interruption class, which shall be calculated in accordance with the following formula:
$$
\frac{a}{b}
$$
where -
a is the sum obtained by adding together the interruption duration factors for all interruptions within the particular interruption class; and
b is the sum obtained by adding together the number of electricity customers affected by each of those interruptions.
| Class | |
|---|---|
| Class A | 288 |
| Class B | 126 |
| Class C | 54 |
| Class D | 46 |
| Class E | 0 |
| Class F | 0 |
| Class G | 54 |
Definitions of Classes:
- Class A: Planned Trans Power Interruption
- Class B: Planned interruption by any Line Operator (other than Trans Power)
- Class C: Unplanned interruption originating within the principal Line Owner's works.
- Class D: Unplanned Trans Power interruption
- Class E: Unplanned ECNZ interruption
- Class F: Unplanned interruption originating from a generator other than ECNZ
- Class G: Other.
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1995, No 91
NZLII —
NZ Gazette 1995, No 91
β¨ LLM interpretation of page content
π
Disclosure of Reliability Performance Measures
(continued from previous page)
π Trade, Customs & IndustryElectricity, Reliability, Interruptions, Faults, SAIDI, SAIFI, CAIDI