Electrical Standards




SEPT. 6.] THE NEW ZEALAND GAZETTE. 2567

TABLE V.—PAPER-INSULATED AND LEAD-COVERED CABLES: CURRENT-
CARRYING CAPACITY AND CORRESPONDING FALL IN PRESSURE.
(Standard Annealed Copper.)

Number and Diameter (Inches) of Wires comprising Conductor.* Nominal Area. Maximum Current permissible (subject to Voltage-drop). Approximate Total Length in Circuit (Lead and Return) for 1-volt drop with Maximum permissible Current (Col. 4).
One Single Cable. Two Single Cables.
1. 2. 3. 4.
1/·036 0·001 5 4·1
1/·044 0·0015 7 6·1
3/·029 0·002 9 7·8
3/·036 0·003 13 12·0
1/·064 0·003 14 12·9
7/·029 0·0045 20 18·2
7/·036 0·007 31 28·0
7/·044 0·01 47 42·0
7/·052 0·0145 63 57·0
7/·064 0·0225 83 75·0
19/·044 0·03 97 87·0
19/·052 0·04 116 104·0
19/·064 0·06 150 135·0
19/·072 0·075 174 157·0
19/·083 0·1 212 191·0
37/·064 0·12 233 210·0
37/·072 0·15 273 246·0
37/·083 0·2 329 296·0
37/·093 0·25 381 343·0
37/·103 0·3 428 385·0
61/·093 0·4 516 464·0
61/·103 0·5 600 540·0
91/·093 0·6 693 624·0
91/·103 0·75 820 738·0
127/·093 0·85 905 815·0
127/·103 1·0 1,035 932·0

*The current-carrying capacity of a conductor having wires of a number or diameter not specified in this table shall be taken to be proportionate to that of the cases specified.

(i) Cables laid together. Multiply amps. for one cable by
3 .. .. .. 0·85
4 .. .. .. 0·80

(ii) Where cable is laid Multiply amps. in above columns by
(a) Cleated to a wall .. .. 0·9
(b) On the solid system .. .. 1·1
(c) Direct in dry earth .. .. 1·2
(d) Direct in wet earth .. .. 1·3
(e) Direct under water .. .. 1·5

(iii) The figures given in the table apply to one single cable, two single cables, and to concentric, twin, and three-core cables run singly.

(iv) The maximum permissible currents (subject to voltage-drop) for the various sizes of conductors up to 1 sq. in. in cross-sectional area are shown in columns 3, 4, 5, and 6 of the table, which allows for a rise in temperature of 50° F. for impregnated-paper cables. For sizes below 0·0145 sq. in. the table is based on a current density of 4,000 amperes per square inch.

(v) The table refers to situations where the temperature of the air does not exceed 80° F., and thus the normal maximum running temperature is 130° F. Impregnated-paper lead-covered cables for pressures not exceeding 660 volts should not be allowed to attain a permanent temperature higher than 176° F., and the figures therefore allow of a margin of 46° F.

(vi) Where the temperature of the air exceeds 80° F. the permissible current shall be reduced in accordance with the following reduction factors:—

Initial Air Temperature.   Amperes permissible to be multiplied by
Degrees F.
90 .. .. .. 0·93
100 .. .. .. 0·85
110 .. .. .. 0·78
120 .. .. .. 0·65
130 .. .. .. 0·54

(vii) The further limitation of the size of conductor by the permissible drop in voltage is dealt with in Regulation 43-21 hereof.



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1935, No 65


NZLII PDF NZ Gazette 1935, No 65





✨ LLM interpretation of page content

🏗️ Paper-Insulated and Lead-Covered Cables: Current-Carrying Capacity and Pressure Drop (continued from previous page)

🏗️ Infrastructure & Public Works
Paper-Insulated Cables, Lead-Covered Cables, Current-Carrying Capacity, Pressure Drop, Electrical Standards