✨ Engineering Tables
SEPT. 6.] THE NEW ZEALAND GAZETTE. 2537
BARE GALVANIZED STEEL—continued.
45,000 lb. BASIS.
(B.) 1/-192 in. (6 S.W.G.).
Constants.—Area, 0·02895 sq. in.; breaking-strength, 2,606 lb.; diameter, 0·192 in.; loading factor, 3·093; maximum tension in conductor, 1,303 lb.; weight, 0·09841 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||
|---|---|---|---|---|---|---|
| 0. | 20. | 40. | 60. | 80. | 100. | |
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Chains. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 5 | 1130 | 1 2 | 1026 | 1 3½ | 923 | 1 5½ |
| 6 | 1060 | 1 10 | 960 | 2 0 | 862 | 2 3 |
| 7 | 982 | 2 8 | 888 | 2 11½ | 798 | 3 3 |
| 8 | 901 | 3 10 | 816 | 4 3 | 736 | 4 8 |
45,000 lb. BASIS.
(C.) 7/-064 in. (7/16 S.W.G.)
Constants.—Area, 0·02252 sq. in.; breaking-strength, 2,026 lb.; diameter, 0·192 in.; loading factor, 3·832; maximum tension in conductor, 1,013 lb.; weight, 0·07785 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||
|---|---|---|---|---|---|---|
| 0. | 20. | 40. | 60. | 80. | 100. | |
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 180 | 945 | 0 4 | 860 | 0 4½ | 776 | 0 5 |
| 220 | 912 | 0 6½ | 828 | 0 6¾ | 745 | 0 7½ |
| 260 | 873 | 0 9 | 790 | 0 10 | 708 | 0 11 |
| 300 | 829 | 1 0½ | 748 | 1 2 | 668 | 1 3½ |
| 340 | 780 | 1 5½ | 701 | 1 7½ | 625 | 1 9½ |
| 380 | 727 | 1 11 | 652 | 2 2 | 580 | 2 5 |
45,000 lb. BASIS.
(D.) 5/-080 in. (5/14 S.W.G.).
Constants.—Area, 0·02513 sq. in.; breaking-strength, 2,362 lb.; diameter, 0·216 in.; loading factor, 3·865; maximum tension in conductor, 1,131 lb.; weight, 0·08679 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||
|---|---|---|---|---|---|---|
| 0. | 20. | 40. | 60. | 80. | 100. | |
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 180 | 1053 | 0 8 | 959 | 0 8½ | 866 | 0 9½ |
| 220 | 1016 | 1 0½ | 923 | 1 1½ | 830 | 1 3½ |
| 260 | 973 | 1 6 | 880 | 1 8 | 790 | 1 10½ |
| 300 | 922 | 2 1½ | 832 | 2 4 | 744 | 2 8 |
| 340 | 867 | 2 11 | 779 | 3 3 | 695 | 3 7 |
| 380 | 808 | 3 10½ | 724 | 4 4 | 645 | 4 10 |
45,000 lb. BASIS.
(E.) 7/-080 in. (7/14 S.W.G.).
Constants.—Area, 0·03519 sq. in.; breaking-strength, 3,166 lb.; diameter, 0·240 in.; loading factor, 3.124; maximum tension in conductor, 1,583 lb.; weight, 0·1216 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||
|---|---|---|---|---|---|---|
| 0. | 20. | 40. | 60. | 80. | 100. | |
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 180 | 1515 | 0 4 | 1382 | 0 4½ | 1251 | 0 4¾ |
| 220 | 1482 | 0 6 | 1351 | 0 6¾ | 1221 | 0 7½ |
| 260 | 1443 | 0 8½ | 1313 | 0 9½ | 1184 | 0 10½ |
| 300 | 1398 | 0 11½ | 1270 | 1 1 | 1144 | 1 2½ |
| 340 | 1349 | 1 3½ | 1223 | 1 5½ | 1100 | 1 7 |
| 380 | 1293 | 1 8½ | 1171 | 1 10½ | 1052 | 2 1 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1935, No 65
NZLII —
NZ Gazette 1935, No 65
✨ LLM interpretation of page content
🏗️
Bare Galvanized Steel Wind Load Tables
(continued from previous page)
🏗️ Infrastructure & Public WorksElectrical Conductors, Wind Load, Sag, Tension, Engineering