Electrical Conductor Tables




2528
THE NEW ZEALAND GAZETTE.
[No. 65

TRIPLE-BRAIDED COPPER—continued.

(B.) 7/·052 in.

Constants.—Area (copper), 0·01483 sq. in.; diameter (covered), 0·327 in.; loading factor, 5·65; maximum tension in conductor, 371 lb.; weight of covered conductor, 0·0882 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 87 4 1
220 .. 78 6 10
260 .. 74 10 0
300 .. 72 13 10
340 .. 70 18 2
380 .. 69 22 11

| 40. | 60. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 78 | 4 7 | 74 | 4 9 |
| 73 | 7 3 | 71 | 7 6 |
| 71 | 10 6 | 70 | 10 8 |
| 70 | 14 3 | 68 | 14 5 |
| 68 | 18 6 | 68 | 18 9 |
| 68 | 23 4 | 67 | 23 7 |

| 80. | 100. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 71 | 5 0 | 68 | 5 3 |
| 69 | 7 8 | 67 | 7 11 |
| 68 | 10 11 | 67 | 11 2 |
| 67 | 14 8 | 66 | 14 11 |
| 67 | 18 11 | 66 | 19 2 |
| 67 | 23 9 | 66 | 23 11 |

(C.) 7/·064 in. (7/16 S.W.G.).

Constants.—Area (copper), 0·0225 sq. in.; diameter (covered), 0·388 in.; loading factor, 4·31; maximum tension in conductor, 562 lb.; weight of covered conductor, 0·1387 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 175 3 2
220 .. 157 5 4
260 .. 148 7 11
300 .. 143 10 10
340 .. 140 14 4
380 .. 138 18 2

| 40. | 60. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 155 | 3 7 | 147 | 3 10 |
| 146 | 5 9 | 141 | 5 11 |
| 141 | 8 4 | 137 | 8 6 |
| 138 | 11 3 | 136 | 11 6 |
| 136 | 14 8 | 134 | 14 11 |
| 135 | 18 6 | 133 | 18 9 |

| 80. | 100. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 139 | 4 0 | 133 | 4 3 |
| 136 | 6 2 | 132 | 6 4 |
| 134 | 8 9 | 131 | 8 11 |
| 133 | 11 8 | 131 | 11 11 |
| 132 | 15 1 | 131 | 15 4 |
| 132 | 18 11 | 131 | 19 1 |

(D.) 7/·083 in.

Constants.—Area (copper), 0·03787 sq. in.; diameter (covered), 0·429; loading factor, 4·530; maximum tension in conductor, 947 lb.; weight of covered conductor, 0·1973 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 587 1 4
220 .. 483 2 6
260 .. 414 4 0
300 .. 373 5 11
340 .. 348 8 2
380 .. 332 10 9

| 40. | 60. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 424 | 1 11 | 365 | 2 2 |
| 375 | 3 2 | 337 | 3 7 |
| 345 | 4 10 | 320 | 5 3 |
| 327 | 6 9 | 309 | 7 2 |
| 316 | 9 0 | 302 | 9 5 |
| 307 | 11 7 | 297 | 12 0 |

| 80. | 100. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 319 | 2 6 | 284 | 2 10 |
| 307 | 3 11 | 282 | 4 3 |
| 299 | 5 7 | 281 | 5 11 |
| 294 | 7 7 | 280 | 7 11 |
| 290 | 9 10 | 280 | 10 2 |
| 288 | 12 5 | 279 | 12 9 |

(E.) 19/·052 in.

Constants.—Area (copper), 0·0403 sq. in.; diameter (covered), 0·482 in.; loading factor, 3·27; maximum tension in conductor, 1,008 lb.; weight of covered conductor, 0·2324 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 595 1 7
220 .. 497 2 10
260 .. 434 4 6
300 .. 396 6 7
340 .. 373 9 0
380 .. 357 11 8

| 40. | 60. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 442 | 2 1 | 390 | 2 5 |
| 399 | 3 6 | 363 | 3 10 |
| 374 | 5 3 | 347 | 5 8 |
| 355 | 7 4 | 337 | 7 9 |
| 343 | 9 10 | 331 | 10 2 |
| 335 | 12 6 | 326 | 12 10 |

| 80. | 100. |
| Ten. | Sag. | Ten. | Sag. |
| lb. | Ft. in. | lb. | Ft. in. |
| 347 | 2 8 | 311 | 3 0 |
| 334 | 4 2 | 310 | 4 6 |
| 327 | 6 0 | 310 | 6 4 |
| 322 | 8 1 | 309 | 8 6 |
| 320 | 10 6 | 309 | 10 11 |
| 317 | 13 2 | 308 | 13 7 |



Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1935, No 65


NZLII PDF NZ Gazette 1935, No 65





✨ LLM interpretation of page content

🏗️ Still-Air Sag and Tension Tables for Electrical Conductors (continued from previous page)

🏗️ Infrastructure & Public Works
Electrical Conductors, Sag, Tension, Tables, Engineering