Electrical Conductor Tables




2520
THE NEW ZEALAND GAZETTE.
[No. 65

DIVISION VIII.—TABLES.

STILL-AIR SAG AND TENSION TABLES FOR ELECTRICAL CONDUCTORS.

MAXIMUM TENSION AND MINIMUM SAG ALLOWABLE.

TABLE I.—BARE (H.D.) COPPER.

Wind, 12 lb. per square foot of diametral plane.

Constants.—Coefficient of thermal expansion = 9·45 × 10⁻⁶ per degree Fahrenheit; maximum allowable stress = 25,000 lb. per square inch; modulus of elasticity = 18 × 10⁶ lb. per square inch.

(A.) 7/·044 in.

Constants.—Area, 0·01064 sq. in.; diameter, 0·132 in.; loading factor, 3·308; maximum tension in conductor, 266 lb.; weight, 0·0418 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20. 40. 60. 80. 100.
Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag.
Ft. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in.
120 239 0 203 0 169 0 137 0 108 0 83 0 11
140 229 0 195 0 162 0 131 0 104 1 0 83 1 3
160 218 0 185 0 154 0 10½ 125 1 1 101 1 4 83 1 8
180 207 0 10 175 0 11½ 145 1 2 120 1 5 99 1 8 82 2 1

(B.) 7/·052 in.

Constants.—Area, 0·01483 sq. in.; diameter, 0·156 in.; loading factor, 2·852; maximum tension in conductor, 371 lb.; weight, 0·0583 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20. 40. 60. 80. 100.
Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag.
Ft. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in.
120 344 0 287 0 243 0 200 0 159 0 8 122 0 10
140 334 0 282 0 229 0 187 0 9 158 0 11 123 1 2
160 323 0 7 268 0 225 0 10 185 1 0 157 1 2 124 1 6
180 311 0 9 263 0 11 221 1 1 181 1 3 155 1 6 125 1 11

(C.) 7/·064 in. (7/16 S.W.G.).

Constants.—Area, 0·0225 sq. in.; diameter, 0·192 in.; loading factor, 2·39; maximum tension in conductor, 562 lb.; weight, 0·0885 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20. 40. 60. 80. 100.
Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag.
Ft. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in.
120 534 0 460 0 387 0 5 317 0 6 252 0 195 0 10
140 524 0 5 451 0 380 0 7 312 0 250 0 10½ 199 1 1
160 515 0 441 0 372 0 9 307 0 11 249 1 2 202 1 5
180 502 0 431 0 10 364 1 0 302 1 2 248 1 5 204 1 9

(D.) 7/·092 in. (7/13 S.W.G.).

Constants.—Area, 0·0465 sq. in.; diameter, 0·276 in.; loading factor, 1·81; maximum tension in conductor, 1,163 lb.; weight, 0·1824 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20. 40. 60. 80. 100.
Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag. Ten. Sag.
Ft. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in. lb. Ft. in.
120 1135 0 981 0 4 830 0 684 0 546 0 7 425 0
140 1126 0 5 974 0 825 0 683 0 8 551 0 437 1 0
160 1115 0 965 0 7 819 0 681 0 10 555 1 448 1 4
180 1103 0 8 955 0 813 0 11 679 1 1 560 1 4 460 1 7


Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1935, No 65


NZLII PDF NZ Gazette 1935, No 65





✨ LLM interpretation of page content

🏗️ Still-Air Sag and Tension Tables for Electrical Conductors

🏗️ Infrastructure & Public Works
Electrical Conductors, Sag, Tension, Tables, Engineering