✨ Electrical Supply Regulations Tables
JULY 12.] THE NEW ZEALAND GAZETTE. 2395
TABLE X.—BARE COPPER-COVERED STEEL.
Wind, 18lb. per square foot of diametral plane.
Constants.--Coefficient of thermal expansion = 7·2 × 10⁻⁶ per degree Fahrenheit ; modulus of elasticity = 20 × 10⁷ lb. per square inch.
NOTE.--This table is for use with wires having a breaking-strength not less than that stated for each size of wire.
(A.) 1/·128 in. (10 S.W.G.).
Constants. — Area, 0·0129 sq. in.; breaking-strength, 1200 lb.; diameter, 0·128 in.; loading factor, 4·315; maximum tension in conductor, 480 lb.; weight, 0·046 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||||
|---|---|---|---|---|---|---|---|---|
| 20. | 40. | 60. | 80. | |||||
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 180 | 424 | 0 5½ | 388 | 0 5⅜ | 352 | 0 6½ | 316 | 0 7 |
| 220 | 397 | 0 8½ | 362 | 0 9¼ | 326 | 0 10 | 292 | 0 11½ |
| 260 | 366 | 1 1 | 332 | 1 2 | 298 | 1 4 | 265 | 1 6 |
| 300 | 332 | 1 7 | 299 | 1 9 | 268 | 1 11 | 238 | 2 2 |
| 340 | 296 | 2 3 | 266 | 2 6 | 238 | 2 10 | 212 | 3 2 |
| 380 | 261 | 3 2 | 235 | 3 7 | 212 | 3 11 | 192 | 4 4 |
| 100. | |||||||||
| Ten. | Sag. | ||||||||
| lb. | Ft. in. | ||||||||
| 280 | 0 8 | 246 | 0 9 | ||||||
| 258 | 1 1 | 226 | 1 3 | ||||||
| 234 | 1 8 | 205 | 1 11 | ||||||
| 210 | 2 6 | 186 | 2 9 | ||||||
| 190 | 3 6 | 170 | 3 11 | ||||||
| 174 | 4 9 | 159 | 5 3 |
(B.) 1/·162 in.
Constants.--Area, 0·02062 sq. in.; breaking-strength, 1800 lb.; diameter, 0·162 in.; loading factor, 3·475; maximum tension in conductor, 720 lb.; weight, 0·073 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||||
|---|---|---|---|---|---|---|---|---|
| 20. | 40. | 60. | 80. | |||||
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 180 | 658 | 0 5½ | 600 | 0 6 | 543 | 0 6½ | 485 | 0 7½ |
| 220 | 629 | 0 8½ | 572 | 0 9½ | 516 | 0 10½ | 460 | 0 11½ |
| 260 | 594 | 1 0 | 538 | 1 2 | 484 | 1 3 | 432 | 1 5 |
| 300 | 556 | 1 6 | 502 | 1 8 | 450 | 1 10 | 402 | 2 1 |
| 340 | 514 | 2 1 | 464 | 2 3 | 417 | 2 6 | 373 | 2 10 |
| 380 | 472 | 2 9 | 426 | 3 1 | 384 | 3 5 | 344 | 3 10 |
| 100. | |||||||||
| Ten. | Sag. | ||||||||
| lb. | Ft. in. | ||||||||
| 430 | 0 8½ | 376 | 0 9½ | ||||||
| 406 | 1 1 | 355 | 1 3 | ||||||
| 381 | 1 7 | 334 | 1 10 | ||||||
| 356 | 2 4 | 315 | 2 7 | ||||||
| 332 | 3 2 | 297 | 3 7 | ||||||
| 312 | 4 3 | 282 | 4 8 |
(C.) 1/·204 in.
Constants.--Area, 0·03278 sq. in.; breaking-strength, 2650 lb.; diameter, 0·204 in.; loading factor, 2·821; maximum tension in conductor, 1060 lb.; weight, 0·116 lb. per foot.
| Span. | Datum. | Degrees Fahrenheit above Datum. | ||||||
|---|---|---|---|---|---|---|---|---|
| 20. | 40. | 60. | 80. | |||||
| Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | Ten. | Sag. | |
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 180 | 987 | 0 5½ | 896 | 0 6¼ | 806 | 0 7 | 715 | 0 8 |
| 220 | 953 | 0 9 | 863 | 0 10 | 776 | 0 11 | 689 | 1 0 |
| 260 | 914 | 1 1 | 827 | 1 2 | 740 | 1 4 | 657 | 1 6 |
| 300 | 869 | 1 6 | 785 | 1 8 | 704 | 1 10 | 627 | 2 1 |
| 340 | 823 | 2 0 | 744 | 2 3 | 668 | 2 6 | 596 | 2 10 |
| 380 | 773 | 2 9 | 698 | 3 0 | 630 | 3 4 | 566 | 3 8 |
| 100. | |||||||||
| Ten. | Sag. | ||||||||
| lb. | Ft. in. | ||||||||
| 629 | 0 9 | 544 | 0 10½ | ||||||
| 605 | 1 2 | 526 | 1 4 | ||||||
| 580 | 1 8 | 509 | 1 11 | ||||||
| 556 | 2 4 | 492 | 2 8 | ||||||
| 532 | 3 2 | 476 | 3 6 | ||||||
| 510 | 4 1 | 461 | 4 6 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1927, No 48
NZLII —
NZ Gazette 1927, No 48
✨ LLM interpretation of page content
🏗️
Electrical Supply Regulations, 1927 (continued)
(continued from previous page)
🏗️ Infrastructure & Public WorksRegulations, Electrical Supply, Public Works Act, Inspections, Fees, Compliance, Dangerous Lines, Penalties, Tables, Constants, Span, Tension, Sag