Electrical Supply Regulations Tables




2390
THE NEW ZEALAND GAZETTE.
[No. 48

(E.) 7/·122 in.

Constants.—Area, 0·0818 sq. in.; diameter, 0·366 in.; loading factor, 5·71; maximum tension in conductor, 983 lb.; weight, 0·0978 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 653 0 7½
220 .. 512 1 2
260 .. 387 2 2
300 .. 306 3 7
340 .. 262 5 5
380 .. 236 7 6

(F.) 7/·134 in.

Constants.—Area, 0·0985 sq. in.; diameter, 0·402 in.; loading factor, 5·21; maximum tension in conductor, 1182 lb.; weight, 0·1178 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 850 0 7
220 .. 703 1 0
260 .. 559 1 9
300 .. 445 3 0
340 .. 374 4 7
380 .. 332 6 5

(G.) 7/·144 in.

Constants.—Area, 0·114 sq. in.; diameter, 0·432 in.; loading factor, 4·87; maximum tension in conductor, 1368 lb.; weight, 0·1362 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 1024 0 6½
220 .. 882 0 11
260 .. 726 1 7
300 .. 591 2 7
340 .. 498 3 11
380 .. 434 5 8

(H.) 7/·149 in.

Constants.—Area, 0·122 sq. in.; diameter, 0·447 in.; loading factor, 4·71; maximum tension in conductor, 1463 lb.; weight, 0·1458 lb. per foot.

Span. Datum. Degrees Fahrenheit above Datum.
0. 20.
Ten. Sag.
Ft. lb. Ft. in.
180 .. 1123 0 6¼
220 .. 976 0 11
260 .. 816 1 6
300 .. 671 2 5
340 .. 564 3 9
380 .. 492 5 4


Next Page →

PDF embedding disabled (Crown copyright)

View this page online at:


VUW Te Waharoa PDF NZ Gazette 1927, No 48


NZLII PDF NZ Gazette 1927, No 48





✨ LLM interpretation of page content

🏗️ Electrical Supply Regulations, 1927 (continued) (continued from previous page)

🏗️ Infrastructure & Public Works
Regulations, Electrical Supply, Public Works Act, Inspections, Fees, Compliance, Dangerous Lines, Penalties, Tables, Constants, Span, Tension, Sag