✨ Electrical Supply Regulations Tables
JULY 12.] THE NEW ZEALAND GAZETTE. 2377
(E.) 19/.052 in.
Constants.—Area, 0.0403 sq. in.; diameter, 0.260 in.; loading factor, 1.923; maximum tension in conductor, 1008 lb.; weight, 0.1582 lb. per foot.
| Span. | Datum. 0. Ten. | Datum. 0. Sag. | 20. Ten. | 20. Sag. | 40. Ten. | 40. Sag. | 60. Ten. | 60. Sag. | 80. Ten. | 80. Sag. | 100. Ten. | 100. Sag. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 120 .. | 979 | 0 3 1/2 | 846 | 0 4 | 716 | 0 4 1/2 | 589 | 0 5 1/4 | 469 | 0 7 1/2 | 364 | 0 9 1/2 |
| 140 .. | 970 | 0 4 3/4 | 838 | 0 5 1/2 | 709 | 0 6 1/2 | 586 | 0 8 | 472 | 0 10 | 374 | 1 0 |
| 160 .. | 958 | 0 6 1/4 | 828 | 0 7 1/2 | 702 | 0 8 3/4 | 583 | 0 10 1/2 | 475 | 1 1 | 383 | 1 4 |
| 180 .. | 946 | 0 8 | 817 | 0 9 1/2 | 696 | 0 11 | 580 | 1 1 | 478 | 1 4 | 392 | 1 8 |
TABLE II.—TRIPLE BRAIDED (H.D.) COPPER.
Wind, 12 lb. per square foot of diametral plane.
Constants.—Coefficient of thermal expansion = 9.45 x 10⁻⁶ per degree Fahrenheit; minimum allowable stress = 25,000 lb. per square inch; modulus of elasticity = 18 x 10⁶ lb. per square inch.
NOTE.—In computing the loading factor for this table the weight and diameter of the covered wire only has been used.
(A.) 7/.038 in. (7/20 S.W.G.).
Constants.—Area (copper), 0.00712 sq. in.; diameter (covered), 0.259 in.; loading factor, 5.16; maximum tension in conductor, 178 lb.; weight of covered conductor, 0.0513 lb. per foot.
| Span. | Datum. 0. Ten. | Datum. 0. Sag. | 20. Ten. | 20. Sag. | 40. Ten. | 40. Sag. | 60. Ten. | 60. Sag. | 80. Ten. | 80. Sag. | 100. Ten. | 100. Sag. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 120 .. | 61 | 1 6 | 54 | 1 9 | 48 | 1 11 | 43 | 2 2 | 40 | 2 4 | 37 | 2 6 |
| 140 .. | 51 | 2 6 | 47 | 2 8 | 43 | 2 11 | 41 | 3 1 | 38 | 3 4 | 36 | 3 6 |
| 160 .. | 46 | 3 7 | 43 | 3 9 | 41 | 4 0 | 39 | 4 3 | 37 | 4 5 | 36 | 4 7 |
| 180 .. | 43 | 4 10 | 41 | 5 1 | 40 | 5 3 | 38 | 5 6 | 37 | 5 8 | 35 | 5 10 |
(B.) 7/.044 in.
Constants.—Area (copper), 0.01064 sq. in.; diameter (covered), 0.280 in.; loading factor, 4.19; maximum tension in conductor, 266 lb.; weight of covered conductor, 0.0687 lb. per foot.
| Span. | Datum. 0. Ten. | Datum. 0. Sag. | 20. Ten. | 20. Sag. | 40. Ten. | 40. Sag. | 60. Ten. | 60. Sag. | 80. Ten. | 80. Sag. | 100. Ten. | 100. Sag. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 120 .. | 154 | 0 9 1/2 | 128 | 0 11 1/2 | 106 | 1 2 | 90 | 1 5 | 77 | 1 7 | 68 | 1 10 |
| 140 .. | 127 | 1 4 | 108 | 1 7 | 94 | 1 10 | 82 | 2 1 | 73 | 2 4 | 67 | 2 6 |
| 160 .. | 108 | 2 0 | 96 | 2 4 | 85 | 2 7 | 77 | 2 10 | 71 | 3 1 | 66 | 3 4 |
| 180 .. | 96 | 2 11 | 87 | 3 2 | 80 | 3 6 | 74 | 3 9 | 70 | 4 0 | 65 | 4 3 |
(C.) 7/.052 in.
Constants.—Area (copper), 0.01483 sq. in.; diameter (covered), 0.327 in.; loading factor, 3.58; maximum tension in conductor, 371 lb.; weight of covered conductor, 0.0882 lb. per foot.
| Span. | Datum. 0. Ten. | Datum. 0. Sag. | 20. Ten. | 20. Sag. | 40. Ten. | 40. Sag. | 60. Ten. | 60. Sag. | 80. Ten. | 80. Sag. | 100. Ten. | 100. Sag. |
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Ft. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. | lb. | Ft. in. |
| 120 .. | 271 | 0 7 | 227 | 0 8 1/2 | 188 | 0 10 | 155 | 1 0 | 128 | 1 3 | 108 | 1 6 |
| 140 .. | 241 | 0 11 | 203 | 1 1 | 169 | 1 3 | 143 | 1 6 | 123 | 1 9 | 107 | 2 0 |
| 160 .. | 213 | 1 4 | 181 | 1 7 | 155 | 1 10 | 135 | 2 1 | 119 | 2 4 | 107 | 2 8 |
| 180 .. | 188 | 1 11 | 163 | 2 2 | 144 | 2 6 | 128 | 2 9 | 116 | 3 1 | 106 | 3 4 |
Next Page →
PDF embedding disabled (Crown copyright)
View this page online at:
VUW Te Waharoa —
NZ Gazette 1927, No 48
NZLII —
NZ Gazette 1927, No 48
✨ LLM interpretation of page content
🏗️
Electrical Supply Regulations, 1927 (continued)
(continued from previous page)
🏗️ Infrastructure & Public WorksRegulations, Electrical Supply, Public Works Act, Inspections, Fees, Compliance, Dangerous Lines, Penalties, Tables, Constants, Span, Tension, Sag