Electric Lines Regulations




3764
THE NEW ZEALAND GAZETTE.
[No. 111

complied with, a breach of these regulations shall be deemed
to have been committed. If the accuracy of the Council’s
recording voltmeter is questioned by the consumer, a standard
instrument shall be supplied by the Inspecting Engineer, the
readings of which shall be accepted as final.

  1. SWITCHBOARDS.

All switchboards shall be made of and mounted on material
that is not inflammable; and the maximum permissible cur-
rent and temperature in any conductor mounted thereon or
leading thereto shall not exceed the values permitted under
the rules of the Institution of Electrical Engineers of Great
Britain. No conductor at a pressure above 650 volts shall
be exposed on the front of any switchboard, and the back
of any switchboard carrying conductors at a pressure over
650 volts shall be screened off, and accessible only to autho-
rized persons.

All substation switchboards controlling high-pressure or
extra high-pressure circuits shall be provided with two
efficient and independent earth connections, connected in
parallel, to which all frames, instrument-cases, and other
metal parts thereof shall be connected. Means shall be pro-
vided for testing the resistance between these two connections
through the earth. Such tests shall be made at least once a
month, and be recorded.

Every switch intended to be used for breaking a circuit,
and every circuit-breaker, shall be so constructed or arranged
that it cannot with proper care be left in partial contact or
accidentally fall or move into contact when left out of contact.

All switchboard circuits shall be so arranged that the course
of any conductor may be readily identified.

Adequate means of access, free from danger, shall be pro-
vided for every switchboard passage-way; and the following
provisions shall apply to all switchboard working-platforms
and passage-ways, unless the bare conductors, whether over-
head or at the sides of the passage-ways, are otherwise
adequately protected against danger by divisions or screens
or other suitable means:—

(a.) Passage-ways constructed for low-tension switchboards
shall have an overhead clearance of 7 ft. between the con-
ductors and the floor, and a clear width measured from bare
conductor of not less than 3 ft.

(b.) Passage-ways constructed for high-pressure and extra
high-pressure switchboards, other than operating desks or
panels working solely at low pressure, shall have an overhead
clearance of not less than 8 ft., and a clear width measured
from bare conductor of not less than 3 ft. 6 in.

(c.) Bare conductors shall not be exposed on both sides of
the switchboard passage-way unless either (1) the clear width
of the passage is, in the case of low pressure, not less than
4 ft. 6 in., and in the case of high pressure not less than 8 ft.,
in each case measured between bare conductors; or (2) the
conductors on one side are so guarded that they cannot
accidentally be touched.

Suitable means, such as rubber mats and gloves, shall be
provided and used when necessary adequately to prevent
danger.

  1. CIRCUIT-BREAKERS.

All outgoing feeders and distributors from the substation
shall be provided with automatic circuit-breakers or fuses set
to open circuit at 100 per cent. excess current over the rated
full load of such feeder or distributor, with a time-limit not
exceeding ten seconds.

  1. FUSES.

Every fuse shall be either of such construction or so pro-
tected by a switch that the fusible metal may be readily
renewed without danger.

  1. DISTRIBUTION.

The distribution may be carried out either by under-
ground or overhead conductors, provided that if at any time
it is deemed by the Minister to be detrimental to the public
safety for the conductors or any particular class of conductors
to be overhead such conductors shall, on receipt of notification
to that effect from the Minister, and within ten months of
such notification, be laid underground, and all consequent
and necessary alterations made by and at the cost of the
Council.

  1. OVERHEAD ELECTRIC LINES.

The diameter of any conductor in any electric line laid or
erected for the supply of electrical energy shall not be less
than 0·104 in. diameter (No. 12 S.W.G. or 7/20 S.W.G.). If
the material of the conductor is aluminium the conductor
shall be stranded.

  1. STRESSES IN OVERHEAD LINES.

The stress in overhead conductors shall not exceed 25,000 lb.
per square inch for copper, 12,500 lb. per square inch for
aluminium, 34,000 lb. per square inch for steel, and 22,500 lb.
per square inch for iron in the event of a minimum temperature
of 32° Fahrenheit, and a wind-pressure of 18 lb. per square
foot of diametral plane occurring simultaneously in the
case of lines erected outside township limits, and 9 lb. per
square foot of diametral plane in the case of lines within
the township limits. The span between supports and the
sag shall be determined to conform to the above limiting-
stresses.

  1. CLEARANCES FOR OVERHEAD LINES.

Overhead lines at low pressure shall not in any part thereof
be at a less height than 18 ft. from the ground.

Overhead lines at extra high pressure shall not in any part
thereof be at a less height than 23 ft. from the ground.

At road crossings the above minimum heights shall be
increased in each case by 2 ft.

No overhead electric lines shall come within 3 ft. of any
other aerial wires or cables, except where it may be permitted
to pass either set of wires between other wires at a pole or
support.

Overhead electric lines shall be so erected as to be inaccessible
to any person without the use of a ladder or other special
appliance.

The maximum sag shall be computed on the assumption
that the conductor is subject to a temperature of 122° F.

  1. SUPPORTS FOR OVERHEAD LINES.

All metal work attached to or forming part of supports
for extra high-pressure lines shall be effectively earthed.

Every support for an aerial line shall be of durable material,
and properly strengthened against forces due to wind-pressure,
change of direction of line, and unequal length of span. The
factor of safety of such supports, if carrying transmission-
lines only, shall be such that the moment resulting from a
wind-pressure of 30 lb. per square foot of plane surface and
18 lb. per square foot of diametral plane upon a cylindrical
surface upon the lines and supports shall not exceed one-half
the applied moment which is sufficient to cripple the support
if of iron, steel, or ferro-concrete, and shall not exceed one-
fourth of the breaking-stress in the case of wood. The factor
of safety of supports carrying distribution-lines shall be four
in the case of steel, iron, or ferro-concrete, and five in the case
of wood, calculated upon the ultimate strength of material,
assuming the wind-pressure to be 15 lb. per square foot upon
a plane surface and 9 lb. per square foot upon a diametral
plane upon a cylindrical surface.

All aerial wires shall be attached to suitable insulators
carried on cross-arms of suitable material and cross-section,
and they shall be so attached to the insulators or guarded that
they cannot fall away from the supports. Conductors covered
with insulating material shall be so attached that their insula-
tion shall not be impaired where they are secured to the
insulators.

Electric lines may be carried on brackets attached to
buildings; provided they are inaccessible from any window,
balcony, parapet, or other portion of the building without the
use of a ladder or other special appliance.

  1. MAXIMUM LENGTH OF SPAN.

The distance between supports carrying distribution-lines
shall not exceed 150 ft. where the direction of the line is
straight, or 120 ft. where the direction is curved or where
the wires make a horizontal angle at the point of support.

  1. ANGLE OF CROSSING THOROUGHFARES.

Where an aerial line crosses a street the angle between the
line and the direction of the street at the place of crossing
shall not be less than 60°, and the span shall be as short as
possible.

  1. INSULATION OF OVERHEAD LINES.

Electric lines at low pressure shall be insulated throughout
with triple braiding, thoroughly impregnated with water-
proof compound; provided that where circumstances permit
the lines may, with the consent of the Minister, be bare.

Electric lines at extra high pressure shall be bare.

Earthed intermediate conductors may in all cases be bare.

All materials used for insulating electric lines or apparatus
should be of the best quality and thoroughly durable and
efficient, having regard to the conditions of their use.

  1. LOW AND EXTRA HIGH PRESSURE LINES ON SAME POLES.

Low-pressure and extra high-pressure lines shall not be
carried on the same poles or supports except with the consent
of the Minister, who shall prescribe the conditions under
which the electric lines shall be erected.

  1. LOCATION OF OVERHEAD LINES.

Except by permission of the Minister of Telegraphs, or
subject to an agreement between the Post and Telegraph
Department and the Council, all overhead electric lines



Next Page →



Online Sources for this page:

VUW Te Waharoa PDF NZ Gazette 1914, No 111


NZLII PDF NZ Gazette 1914, No 111





✨ LLM interpretation of page content

🏗️ License authorizing the Whangarei Borough Council to erect Electric Lines (continued from previous page)

🏗️ Infrastructure & Public Works
12 October 1914
Electric Lines, License, Whangarei Borough Council, Conditions, Construction