✨ Electricity Supply Regulations
JUNE 26.] THE NEW ZEALAND GAZETTE. 1987
safety of such supports, if of iron, steel, or ferro-con-
crete, taking into consideration all possible stresses,
including wind-pressure at 30 lb. per square foot on
plane surfaces and 18 lb. per square foot of dia-
metrical plane for cylindrical surfaces, shall be such
that the moment resulting from these stresses shall
not exceed one-half the applied moment which will
cripple the supporting structure. The factor of
safety of the support, if of wood, shall be four,
reckoned upon the ultimate strength of the material.
-
Along the transmission-wire route a wire or wires of
hard-drawn copper not smaller than No. 12 standard wire
gauge may be run for service telephone purposes. This wire
shall be bound throughout to double-shed porcelain insulators. -
At the generating and transformer stations the trans-
mission-wires shall be securely and safely led in ; and pro-
tection against lightning shall be provided at each end of the
lines. The telephone wire or wires shall be suitably guarded
against lightning, shall be fused, and such arrangements shall
be made where the telephone is placed as will prevent the
possibility of injury resulting to any person using the tele-
phone should a power-wire come into contact with the tele-
phone wire. -
Where conductors cross telegraph or telephone lines
they shall be insulated and protected by the licensee to the
satisfaction of the Minister of Telegraphs. -
The transmission-line shall be on the opposite side of
the road or street to that on which the telegraph and tele-
phone lines are run, and where there are no telegraph or
telephone wires the licensee shall erect his lines on one side
of the road or street only. It shall be patrolled throughout
its whole length at least once a week, and its insulation shall
be so maintained that the maximum leakage shall not exceed
one-thousandth part of the maximum supply current. Suit-
able means shall be provided for indicating leakage on the
line. Every leakage shall be remedied without delay. Tests
shall be made weekly, and recorded by the licensee. -
Transformers shall have easily removable fuses for the
primary circuit, and shall, as far as possible, be installed in
small enclosures accessible only to the licensee’s officers or
servants. Transformers for use outside shall be fitted with
watertight cast-iron cases, and shall be affixed to poles so as
to be inaccessible except by the use of a ladder or other
special appliance. Every transformer shall have its iron case
effectively connected with earth. -
Conductors used for making the lightning-guard and
transformer-case earth connections shall be of copper, and
shall have an area of at least 0·023 square inches. They
shall be properly stapled or fastened to the supports, and
shall be protected by a batten for a distance of 8 ft. from the
ground. They shall be run as straight as possible, and be
properly connected to an earth-plate. A test shall be made
every three months, and oftener if required, of all earths, to
ensure that the earth-wire is intact and that the earth is
effective. -
Where poles are carrying low-tension wires, the spans
shall not exceed 200 ft. where the direction of the line is
straight, or 150 ft. where the direction is curved or where
the wires make a horizontal angle at the point of support. -
Low-tension distribution shall be carried out on the
single-phase system at a pressure of 230 to 250 volts. The
supply to street lamps, incandescent lamps, and to private
consumers shall be at a pressure of 230 volts.
Where cables are led to and from transformer enclosures
they shall be protected on the poles by being run in iron pipe,
which shall be effectively earthed.
Low-tension wires or cables shall be covered with a triple
braiding impregnated with waterproof compound, except
where otherwise provided for.
-
Where the erection of the electric lines or wires necessi-
tates the alteration of existing telegraph or telephone lines or
wires, the expense of such alteration shall be borne by the
licensee. -
The sectional area of the conductor in any electric line
for distribution purposes laid or erected in any street shall
not be less than the area of a No. 10 S.W.G. wire. -
All material used for insulating electric lines or appa-
ratus shall be of the best quality, and thoroughly durable
and efficient, having regard to the conditions of its use. Suit-
able provision shall be made where necessary for the protec-
tion of the insulating material against injury or removal. If
the protection so provided is wholly or partly metallic it
shall be efficiently connected with earth. -
Any metallic body to be “efficiently connected with
earth” shall be connected with the general mass of the earth
in such manner as will ensure at all times an immediate and
safe discharge of electrical energy. -
Every support for an aerial line for distribution pur-
poses shall be properly stayed against forces due to wind-
pressure, change of direction of the line, or unequal lengths
of span. The factor of safety shall be for all aerial lines and
for all other parts of the structure at least 6, and for aerial
wires at least 4, taking the maximum possible wind-pressure
at 30 lb. per square foot.
-
The low-tension wires shall be attached to double-shed
porcelain insulators carried on cross-arms of suitable material
and cross-section, and they shall be so attached to the insu-
lators or guarded that they cannot fall away from the support. -
Any aerial wire used for low-tension distribution or for
telephone service shall not in any part thereof be at a less
height from the ground than 18 ft., or within 5 ft. measured
horizontally or vertically from any building or erection other
than a support for the line, except where brought in to a
building for the purpose of supply. -
Service lines from aerial lines shall be led as directly
as possible to insulators firmly attached to some portion of
the consumer’s premises which is not accessible to any person
without the use of a ladder or other special appliance. Every
portion of any service line which is outside a building but is
within 7 ft. from any part of the building shall be rubber-
insulated. -
Where an aerial wire crosses a street, the angle between
the line and the direction of the street at the place of crossing
shall not be less than 60°, and the spans shall be as short as
possible. -
Where an aerial line crosses or is in proximity to any
metallic substance, precautions shall be taken by the licensee
against the possibility of the line coming into contact with
the metallic substance by breakage or otherwise. -
Where telegraph or telephone wires are crossed either
over or under by the low-pressure electric-light wires, there
shall be a distance of at least 2 ft. between the telephone and
the electric-light wires, and the former shall, if deemed neces-
sary, be insulated throughout the whole length of the span
intersected, and when the crossing is at a telegraph or tele-
phone pole the spans on each side of the pole shall be
insulated by the licensee, if required by the Minister of
Telegraphs. The low-pressure wires shall, where deemed
necessary, be rubber-insulated at such crossings either over
the whole span or over such portion of it as will ensure that
uninsulated portions of the telegraph or telephone and of the
low-tension electric-light wires shall not come into contact
with each other. In cases where it may be deemed not
necessary to insulate both classes of wires, either the tele-
graph and telephone or the electric-light wires shall be insu-
lated as may be considered most suitable by the Minister of
Telegraphs. Where it may be required to cross through
telegraph or telephone wires with low-tension distribution-
wires, the latter shall be affixed to porcelain insulators
mounted on iron brackets suitably attached to the arms
on each side of the line being passed through, and then
taken through bell-mouthed iron pipes secured to the arms.
The iron pipe and brackets shall be efficiently earthed. The
low-pressure wires shall be insulated with vulcanized rubber
of 600-megohms-per-mile grade, and the insulation shall ex-
tend as is indicated in the preceding part of this clause.
The cost of insulating the telegraph and telephone wires
shall be borne by the licensee.
Due notice in writing shall be given to the Telegraph
Engineer of the district or his deputy of all works involving
the crossing or intersection of telegraph or telephone wires.
No attempt shall be made to utilize telegraph or telephone
poles as supports for low tension wires until the consent of
the Telegraph Engineer of the district or his deputy shall
first have been obtained, and such applications shall be con-
fined strictly to those cases where no other practicable means
of overcoming the difficulty are available.
-
Efficient guard-wires or other suitable protection shall,
if required by the Minister of Telegraphs, be erected in a
manner to meet with the approval of the said Minister at
all crossings and places where either transmission or distri-
bution electric-lighting wires intersect telegraph or telephone
wires. The licensee shall bear the expense of such guard-
wires or other protective devices in all cases where an
electric-lighting wire intersects a telegraph or telephone wire
previously existing. -
Every aerial line, including its supports, its conductors,
and their insulating covering, and all the structural parts and
electrical appliances and devices belonging to or connected
with the line shall be duly and efficiently supervised and
maintained by the licensee as regards both electrical and
mechanical conditions. -
An aerial line shall be removed so soon as it has ceased
to be used for the transmission of electricity, unless the
licensee intends within a reasonable time again to take it
into use. -
All metal pipes or coverings containing any electric line
or wire shall be efficiently connected with earth, and shall be
so jointed as to make good electrical connection throughout
their whole length. -
The licensee shall be responsible for all electric lines,
fitting, and apparatus belonging to him, or under his control
Next Page →
Online Sources for this page:
VUW Te Waharoa —
NZ Gazette 1913, No 49
NZLII —
NZ Gazette 1913, No 49
✨ LLM interpretation of page content
🏗️ Conditions and Specifications for Electricity Supply Lines
🏗️ Infrastructure & Public WorksTransmission lines, electrical safety, insulators, lightning protection, transformers, earth connections, low-tension distribution, voltage, wire gauge, material quality, pole supports, maintenance, removal of lines, electrical regulations
- Minister of Telegraphs